Accu/Line™
Accu/Line™ Hi
Welker’s turnkey natural gas injection odorization solution for flow rates from 1 Mscfh up to 70 MMscfh and a maximum operating pressure of 1800 psig.
The intuitive touch screen controller is the brains of the operation. Receiving feedback from the customer gas flow meter and system odorant flow meter, the controller adjusts the injection rate to changing flow conditions, ensuring continuous proportional to flow odorization. Measuring every pump stroke volume to an accuracy of 0.002 cc, the system odorant flow meter guarantees precise odorant injection.
Monitor and troubleshoot the Accu/Line™ on-site at the touch screen controller or remotely via Modbus to ensure optimal system performance. Access time- and date‑stamped historical records saved to the installed microSD card for accurate reporting, planning, and scheduling.
Improve system responsiveness to variations in flow rate with two odorant injection pumps of different volumes, or limit interruptions to operation with identical redundant pumps. The Welker F-9 Filter and Welker F-5 Filter Dryer prolong the operational life and reliability of the pumps by removing contaminants from the odorant and pneumatic supplies.
From 5 gallons to 10,000 gallons, the odorant supply tank can be sized to suit a broad range of flow rates. Regardless of volume, each tank comes with 110% containment sloped to the drain to protect against contamination and ease clean up.
Accu/Line™ | |
---|---|
Materials of Construction | Lo: 316/316L Stainless Steel, Anodized Aluminum, Buna, Kalrez® Collection Cup and Dynamic Seals, PTFE, Viton® Static Seals Standard: 316/316L Stainless Steel, Anodized Aluminum, Kalrez®, PTFE Hi: 316/316L Stainless Steel, Anodized Aluminum, Kalrez®, PTFE |
Power | DC 24 V |
AC 120 V | |
Optional Solar Panel | |
Injection Outlet Connection | 1/4" Tubing |
Instrument Gas Connection | 3/8" Tubing |
Odorant Inlet Connection | 3/8" Tubing |
Vent Connection | 3/8" Tubing |
Odorant Inlet Pressure Required | 10 psig–50 psig |
Instrument Gas Pressure Required | Lo: 15 psig–70 psig Standard: 30 psig–225 psig Hi: 30 psig–225 psig |
Injection Volume | Lo: 0.06 cc, 0.2 cc, or 0.5 cc Standard: 0.5 cc–10 cc Hi: 10–150 cc |
Injection Rate | Lo: Up to 10 Injections/Minute Standard: Up to 5 Injections/Minute Hi: Up to 3 Injections/Minute |
Odorant Tank Volume | 120 US Gallons |
250 US Gallons | |
500 US Gallons | |
1000 US Gallons | |
Ambient Temperature | -20 °F to 120 °F |
Operating Pressure | 1800 psig |